starting frequency for the Variable Speed Oil Pump is 45.0 Hz. The start inhibit is released when the
motor current decreases to less than 15% and the Warning Reset button is pressed on the display.
A full System Coastdown is performed when this fault is released.
VSD – Frequency > 0 Hz
This start inhibit is set whenever the chiller is shutdown and a Compressor Motor Variable Speed
Drive (VSD) Output Frequency of greater than 0 Hz is detected. This fault is released and the chiller
can be started after the operator presses the Clear Faults button. The oil pump is started (with a
starting frequency of 45 Hz) as soon as this fault is detected. A System Coastdown is performed
whenever this fault is released.
LCSSS – High Temperature Phase X - Stopped
(Mod. “B” Solid State Starter only)
The chiller is stopped and the Liquid Cooled Solid State Starter Logic/Trigger Board has detected
that the temperature of phase A, B, or C (designated as X in this message) Silicon Controlled
Rectifier (SCR) Module is greater than 110°F. The starter cooling pump will run and the chiller will
be inhibited from starting until the temperature decreases to less than 109°F.
Warning messages
Warning – Condenser or Evaporator XDCR Error
The Evaporator Pressure transducer is indicating a higher pressure than the Condenser pressure
transducer after the chiller has been running for 10 minutes. This is indicative of a Condenser or
Evaporator transducer failure. This message will be displayed until the condition clears and the
WARNING RESET Keypad key is pressed in Operator (or higher) access mode. Condition not checked
in Brine mode.
Warning – Standby Lube – Low Oil Pressure
A minimum of 15 PSID of oil pressure was not achieved in the first 30 seconds of a Standby
Lubrication cycle, or the pressure decreased below this value during the remainder of the cycle.
This message will be displayed and no further Standby Lubrications will be performed until the
WARNING RESET key is pressed in Operator (or higher) access mode.
This warning is also set when either the Pump Oil Pressure transducer or the Sump Oil Pressure
transducer is less than 2 PSIG when a Standby Lube is requested by automatic control. This inhibits
the Standby Lube cycle when the chiller is open to atmosphere.
Warning – Setpoint Override
A failure of the FeRAM memory device was detected during the initialization process that occurs
when power is applied to the Control Center. Due to this failure, any or all of the programmed
Setpoints could have been corrupted. Therefore, all Setpoints have been automatically changed to
their Default values. All Setpoints will have to be programmed to their desired values. This message
will clear when the WARNING RESET key is pressed in Operator (or higher) access mode.
Warning – Condenser – High Pressure Limit
The Condenser Pressure exceeds the High Pressure Warning Setpoint threshold, programmed
by a Service Technician logged in at SERVICE access level. While this condition is in effect, the Pre-
rotation Vanes are inhibited from further opening. This message automatically clears and the Vanes
are permitted to open when the condenser pressure decreases to 5 PSIG below the Setpoint.
Warning – Evaporator – Low Pressure Limit
The Evaporator Pressure has decreased to the Warning threshold. This threshold is fixed in Water
cooling applications. In Brine cooling applications, the threshold is a fixed amount above the
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
168
Содержание YK Style H
Страница 2: ...2 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 6: ...6 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 202: ...Figure 87 Sample printout status cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 202...
Страница 203: ...Figure 88 Sample printout setpoints 203 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 204: ...Figure 89 Sample printout setpoints cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 204...
Страница 205: ...Figure 90 Sample printout schedule 205 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 206: ...Figure 91 Sample printout sales order Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 206...
Страница 207: ...Figure 92 Sample printout sales order cont 207 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 208: ...Figure 93 Sample printout history Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 208...
Страница 209: ...Figure 94 Sample printout history cont 209 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...