Table 10: Display only fields
Field/LED name
Description
Oil Pressure
Displays the pressure differential between the high side oil pressure transducer
(output of oil filter) and the low side oil pressure transducer (compressor housing).
The displayed value includes offset pressure derived from auto-zeroing during the
System Prelube. If either of the transducers used to calculate this differential is out of
range, the display field will show XX.X. This is only displayed when a Variable Speed Oil
Pump is installed.
Chilled Liquid Temperature –
Entering
Displays the temperature of the liquid as it enters the evaporator.
Chilled Liquid Temperature –
Leaving
Displays the temperature of the liquid as it leaves the evaporator.
Chilled Liquid Temperature –
Setpoint
Displays the active temperature setpoint to which the chiller is controlling the
evaporator liquid. This value could come from a 4 mA to 20 mA, 0 VDC to 10 VDC, 1 to
11 second PWM signal, communicated through an SC-EQ interface in BAS mode, or a
locally programmed value when in Local mode of operation.
Heating Condenser Liquid
Temperature – Leaving
Displays the temperature of the liquid as it leaves the heating condenser tube bundle.
Only displayed when the Heat Recovery is enabled.
Heating Condenser Liquid
Temperature – Return
Displays the temperature of the liquid as it enters the heating condenser tube bundle.
Only displayed when the Heat Recovery is enabled.
Heating Condenser Liquid
Temperature – Active Hot Water
Setpoint
Displays the Hot Water Setpoint to which the Leaving Heating Condenser Liquid
Temperature is being controlled. Only displayed when Heat Recovery is enabled and
Hot Water Control is enabled.
Evaporator Pressure
Displays the present refrigerant pressure in the evaporator.
Evaporator Saturation
Displays the present saturation temperature in the evaporator.
Programmable
None
Table 11: Navigation
Button
Access level
Description
Home
View
Returns user to Home screen.
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
32
Содержание YK Style H
Страница 2: ...2 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 6: ...6 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 202: ...Figure 87 Sample printout status cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 202...
Страница 203: ...Figure 88 Sample printout setpoints 203 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 204: ...Figure 89 Sample printout setpoints cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 204...
Страница 205: ...Figure 90 Sample printout schedule 205 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 206: ...Figure 91 Sample printout sales order Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 206...
Страница 207: ...Figure 92 Sample printout sales order cont 207 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 208: ...Figure 93 Sample printout history Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 208...
Страница 209: ...Figure 94 Sample printout history cont 209 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...