Table 172: Master slots numbers list for use with Trend feature
Slot
number
Description
Slot
number
Description
2305
Motor: Is Motor Starter On
8199
VSOP: Manual Command Frequency
2306
Motor: Current %FLA
8200
VSOP: Is Pulldown In Effect
2307
Motor: Is Motor Controller Switch Open
8201
VSOP: Pulldown Time Remaining
2308
Motor: Current Limit Local Setpoint
8202
VSOP: Target Setpoint
2309
Motor: Current Limit Remote Analog Setpoint
8203
VSOP: Pressure Setpoint
2310
Motor: Current Limit Remote BAS Setpoint
8204
VSOP: Control Period
2311
Motor: Current Limit Remote Modem Setpoint
8205
Refrigerant Level: Is Control Enabled
2312
Motor: Current Limit Selected Setpoint
8206
Refrigerant Level: Position
2313
Motor: Pulldown Demand Time Remaining
8207
Refrigerant Level: Is Valve Closing
2314
Motor: Pulldown Demand Limit Setpoint
8208
Refrigerant Level: Is Valve Opening
2315
Motor: Pulldown Demand Time Setpoint
8209
Refrigerant Level: Control Mode
2316
Motor: Anti-Recycle Time Remaining
8210
Refrigerant Level: Is Pulldown In Effect
2317
Motor: Current Limit Remote Digital Setpoint
8211
Refrigerant Level: Pulldown Time Remaining
2351
Motor - Operating Hours Since last Lubrication
8212
Refrigerant Level: Target Setpoint
Mod "A" Solid State Starters
8213
Refrigerant Level: Setpoint
2560
SSS: Phase A Current
8214
Refrigerant Level: Period
2561
SSS: Phase B Current
8215
Refrigerant Level: Proportional Limit Close
2562
SSS: Phase C Current
8216
Refrigerant Level: Proportional Limit Open
2563
SSS: Phase A Voltage
8217
Refrigerant Level: Rate Limit Close
2564
SSS: Phase B Voltage
8218
Refrigerant Level: Rate Limit Open
2565
SSS: Phase C Voltage
8222
HSTB: Is Solenoid Installed
2566
SSS: Scale/Model
8223
HSTB: Is Solenoid On
2567
SSS: Full Load Amps
8224
HSTB: Proximity Position
2568
SSS: Supply Voltage Range
8225
HSTB: Proximity Differential
2569
SSS: Is Current Unbalance Check Enabled
8226
HSTB: Proximity Reference Position
Mod "B" Solid State Starters
8280
Stall Detector Board output voltage
2570
LCSSS: Input Power
8281
VGD open
2571
LCSSS: Kilowatt Hours
8282
VGD close
2572
LCSSS: Phase A Current
8317
Stall DC Pressure Voltage
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
164
Содержание YK Style H
Страница 2: ...2 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 6: ...6 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 202: ...Figure 87 Sample printout status cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 202...
Страница 203: ...Figure 88 Sample printout setpoints 203 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 204: ...Figure 89 Sample printout setpoints cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 204...
Страница 205: ...Figure 90 Sample printout schedule 205 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 206: ...Figure 91 Sample printout sales order Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 206...
Страница 207: ...Figure 92 Sample printout sales order cont 207 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 208: ...Figure 93 Sample printout history Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 208...
Страница 209: ...Figure 94 Sample printout history cont 209 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...