Table 117: Programmable
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Head Pressure
Control
Service
JCI Service
Allows a Service Technician to enable or disable the Head Pressure
Control feature. Head Pressure Control cannot be used simultaneously
with Heat Pump Duty. When Heat Pump Duty is enabled, Head Pressure
Control is automatically disabled and locked.
Power Failure
Restart
Operator
Standard
Allows the user to select Manual or Automatic restart after power failure.
Motor
Monitoring
Service
JCI Service
Allows the Service Technician to enable or disable the Motor Monitoring
feature.
Evaporator
Transducer
Service
JCI Service
Allows the Service Technician to select the appropriate evaporator
transducer for a standard (6 -74) or heat recovery (1 - 125) chiller
Motor Auto
Lube Type
Service
JCI Service
Allows the Service Technician to select QLS401, P203, Sleeve or None as
appropriate.
Heat Pump
Duty
Admin
Admin
Allows the Service Technician to enable and disable the Heat Pump
feature. The access level must be ADMIN and the Refrigerant Type must
be set to R-134a (SW1- 1) for the setpoint to appear on this screen When
Heat Pump Duty is enabled, Heat Recovery and Head Pressure Control are
automatically disabled and locked.
Variable Water
Outlet Control Service
JCI Service
Allows the Service Technician to enable or disable Variable Water Outlet
Control to meet European CE requirements. When Variable Water Outlet
Control is Enabled on the Setup Screen, the local and remote cooling
setpoints are ignored and the Selected Cooling Setpoint is set based on
the Entering Condenser Liquid Temperature as follows:
Entering condenser liquid
temperature
Selected cooling setpoint
ECLT ≥ 82.4°F (28°C)
44.6°F (7°C)
75.2°F (24°C) ≤ ECLT < 82.4°F (28°C)
47.3°F (8.5°C)
68.0°F (20°C) ≤ ECLT < 75.2°F (24°C)
50.0°F (10°C)
ECLT < 68.0°F (20°C)
52.7°F (11.5°C)
The selected setpoint is ramped at 0.1°F/sec when changing between
values in the table.
Table 118: Navigation
Button
V09 software
and earlier
V10 and later
with YORK
Chiller Access
Manager
Description
Home
View
View
Returns the user to Home Screen.
Schedule
View
View
Navigates to the subscreen allowing definition of the chiller operation
schedule.
User
View
View
Navigates to the subscreen allowing configuration of user preferences.
Comms
View
View
Navigates to the subscreen allowing configuration of system
communications.
Printer
View
View
Navigates to the subscreen allowing configuration and control of printer
functions.
Sales Order
View
View
Navigates to the subscreen displaying the sales order information for the
chiller system.
Operations
View
View
Moves to the subscreen displaying operating parameters of the chiller
system.
Diagnostics
Service
JCI Service
Navigates to the subscreen allowing limited diagnostic capability while
operating.
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
120
Содержание YK Style H
Страница 2: ...2 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 6: ...6 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 202: ...Figure 87 Sample printout status cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 202...
Страница 203: ...Figure 88 Sample printout setpoints 203 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 204: ...Figure 89 Sample printout setpoints cont Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 204...
Страница 205: ...Figure 90 Sample printout schedule 205 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 206: ...Figure 91 Sample printout sales order Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 206...
Страница 207: ...Figure 92 Sample printout sales order cont 207 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...
Страница 208: ...Figure 93 Sample printout history Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center 208...
Страница 209: ...Figure 94 Sample printout history cont 209 Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center...