SECTION 3 - HANDLING, STORAGE, INSTALLATION AND REASSEMBLY
FORM 155.32-ICOM2.EN.UL
ISSUE DATE:1/10/2018
26
JOHNSON CONTROLS
STRUCTURAL SUPPORT AND INSTALLATION
Structural support of the unit should be provided as indicated for maximum efficiency.
Maintain adequate maintenance space around the chiller-heater so work can be safely
performed. In non-seismic areas Johnson Controls recommends foundation bolts be
installed in level concrete to secure the unit and prevent shifting.
It is the customer’s responsibility to furnish the foundation bolts, nuts and washers when
used. Rubber vibration isolator pads must be fitted to the unit base before installation as
shown in
Vibration and Isolation Details on page 29
. The tolerance for leveling is 1 inch in
1,000 inches or 1 mm in 1,000 mm.
Apply thermal insulation to the chiller-heater. See
Insulating and Material Thickness
.
See
.
Be sure to install insulation or a fence around the exhaust gas duct
outer cover to prevent burns or a fire.
For dimensions see
and
. For the external
dimensions of the unit and foundation, see the full view of the unit and the foundation
drawing. For serviceability and maintenance, leave a minimum of 1,000 mm space on all
sides of the chiller-heater. To ensure there is adequate clearance for tube removal, the
maintenance space at the end of the unit should equal 1.25 x the length of the unit.
INDOOR AND OUTDOOR INSTALLATION
This chiller-heater is designed to be used indoors. Exposure to the elements can
compromise the integrity of the thermal insulation. Minimum allowable temperature for
outdoor installation is 32°F, provided that the chiller-heater includes the cold ambient
option. Outdoor installations will be considered on a case-by-case basis by a Johnson
Controls Service Representative and proper instruction for installation will be provided at
that time.
When installing the unit indoors, have a specialized company provide a suitable flue/
smokestack and air supply/exhaust equipment. Insufficient air supply or improper exhaust
can cause oxygen starvation and a fire. The interlock of the control panel should be set up
with a supply/exhaust fan to create a proper draft.
ELECTRICAL
The electrical work must be performed in accordance with the wiring diagrams, delivery
specifications, and technical standards for electrical equipment found in
. Use the specified cables to complete the wiring, and fasten them to
the according terminals securely. Loose fitting cables can cause the terminals to heat up,
resulting in fire or electrical shock. Electrical work must be supervised or completed by a
Johnson Controls Service Representative.
CAUTION: Waterproof the floor on which the unit will be installed in case of future leaks.
CAUTION: Do not install a chimney near the air supply.
NOTE: A ground fault (earth leakage) circuit breaker is not installed for this chiller-heat-
er unit. Install an adequate ground fault circuit breaker at the primary side of the chiller-
heater unit.
Содержание YHAU-CGH
Страница 14: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 14 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 38: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 38 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 55: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 JOHNSON CONTROLS 55 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 57: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 57 LD27463...
Страница 59: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 59 LD27465...
Страница 61: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 61 LD27471...
Страница 63: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 63...
Страница 65: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 65 LD27477...
Страница 67: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 67 LD27479...
Страница 69: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 69 LD27475...
Страница 160: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 160 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 170: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 170 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 172: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 172 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 181: ...FORM 155 32 ICOM2 EN UL APPENDIX 1 CHECKLIST ISSUE DATE 1 10 2018 JOHNSON CONTROLS 181 NOTES...