Table 41 -
Chilled/Hot and Cooling Water Quality Control (Maximum Concentrations)
NOTES:
1. The item names, their definitions, and units are based on JIS K 0101. Units and figures in braces are those which were used formerly. They are shown here for reference purposes.
2. In the “Tendency” column, a white circle (O) indicates that a particular item is a factor in corrosion/scale formation.
3. Generally speaking, when the water temperature is high (104°F (40°C) or higher), corrosion develops noticeably. Especially when steel material which makes direct contact with water has
no protective covering, it is desirable to provide a suitable corrosion-preventive measure, such as adding a corrosion-preventive agent or applying deaeration treatment.
4. In a cooling water system using a closed cooling tower, the closed-circuit circulating water and its replenishment water shall meet the quality standards for a hot water system, and the
sprinkling water and its replenishment water shall meet the quality standards for a circulation-type cooling water system.
5. The supply water and replenishment water shall be tap water, industrial water, or ground water. Do NOT use demineralized water, neutral water, or softened water.
6. The items shown above are representative factors in corrosion and scale formation.
ELEMENT
(1) (6)
COOLING WATER SYSTEM
(4)
CHILLED/HOT WATER
SYSTEM
TENDENCY
(2)
CIRCULATING
TYPE
NON-
CIRCULATING
WATER
CIRCULATING
WATER
REPLENISH
WATER
PASSING
WATER
CIRCULATING
WATER
(20°C OR
LOWER)
REPLENISH
WATER
CORROSION
SCAL
E
FO
RMIN
G
ST
ANDA
RD IT
EMS
pH 77 °F (25 °C)
6.5~8.2
6.0~8.0
6.8~8.0
6.8~8.0
6.8~8.0
O
O
Electric Conductivity (mS/
m) 77 °F(25 °C)
(µS/cm) 77 °F(25 °C)
(1)
Max. 80
(Max. 800)
Max. 30
(Max. 300)
Max. 40
(Max. 400)
Max. 40
(Max. 400)
Max. 30
(Max. 300)
O
O
Chloride Ion
(mgCl
¯
/l)
Max. 200
Max. 50
Max. 50
Max. 50
Max. 50
O
Sulfulic Acid Ion (mgSO
4
2¯
/
I)
Max. 200
Max. 50
Max. 50
Max. 50
Max. 50
O
Acid Consumption (PH4.8)
(mgCaCO
3
/I)
Max. 100
Max. 50
Max. 50
Max. 50
Max. 50
O
Total Hardness
(mgCaCO
3
/I)
Max. 200
Max. 70
Max. 70
Max. 70
Max. 70
O
Calcium Hardness
(mgCaCO
3
/I)
Max. 150
Max. 50
Max. 50
Max. 50
Max. 50
O
Ionized Silica (mgSiO
3
/I)
Max. 50
Max. 30
Max. 30
Max. 30
Max. 30
O
REFERENC
E I
T
EMS
Iron (mgFe/I)
Max. 1.0
Max. 0.3
Max. 1.0
Max. 1.0
Max. 0.3
O
O
Copper (mgCu/I)
Max. 0.3
Max. 0.1
Max. 0.1
Max. 0.1
Max. 0.1
O
Sulfurization Ion (mgS
2¯
/I)
NO IONS ALLOWED
O
Ammonium Ion (mgNH
4
+/I)
Max. 1.0
Max. 0.1
Max. 1.0
Max. 1.0
Max. 0.1
O
Residual Chlorine (mgCI/I)
Max. 0.3
Max. 0.3
Max. 0.3
Max. 0.3
Max. 0.3
O
Free Carbonate Acid
(mgCO
2
/I)
Max. 4.0
Max. 4.0
Max. 4.0
Max. 4.0
Max. 4.0
O
Stability Index
6.0~7.0
–
–
–
–
O
O
Содержание YHAU-CGH
Страница 14: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 14 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 38: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 38 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 55: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 JOHNSON CONTROLS 55 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 57: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 57 LD27463...
Страница 59: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 59 LD27465...
Страница 61: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 61 LD27471...
Страница 63: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 63...
Страница 65: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 65 LD27477...
Страница 67: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 67 LD27479...
Страница 69: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 69 LD27475...
Страница 160: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 160 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 170: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 170 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 172: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 172 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 181: ...FORM 155 32 ICOM2 EN UL APPENDIX 1 CHECKLIST ISSUE DATE 1 10 2018 JOHNSON CONTROLS 181 NOTES...