WET STORAGE METHOD
The wet storage method may be used when there is no concern about water freezing in
winter. Store the machine in a place where the ambient temperature will remain higher than
32°F (0°C).
If it is likely that the temperature will drop below 32°F (0°C), provide a heater for the
machine. If a heater is not possible, contact your local Johnson Controls service center for
further information. For details on the wet storage method, see
.
The wet storage procedure is as follows if either chilled/hot line or the cooling water line is
an open system:
1. Completely drain the water from the systems if it has deteriorated in quality.
2. Clean the water systems by passing clear water through them from a position higher
than the chiller-heater.
3. Fill the water systems with clear water.
4. Circulate the clear water through the water pump for 30 minutes to one hour to clean
it.
5. Drain the water.
6. Completely fill the water systems with clear water again.
7. Store the machine.
DRY STORAGE METHOD
The dry storage method should be used if the chilled/hot water system or the cooling water
system may freeze in the winter or, if the water system has a lining tube.
The dry storage procedure is as follows if either the chilled/hot line or the cooling water line
is an open system:
1. Completely drain the water.
2. Clean the water systems by passing clear water through them from a position higher
than the chiller-heater.
3. Fill the water systems with clear water.
4. Circulate the clear water through the water pump for 30 minutes to one hour to clean
it.
5. Drain the water from each waterbox.
6. Dry the interior of each waterbox and the heat transfer tube.
7. Store the machine.
PRECAUTIONS AGAINST EXTERNAL DAMAGE
Avoid storing the machine in a place that is easily accessible or near a construction site. If
this is unavoidable, provide the machine with protection.
If it is not possible to protect the machine, fill the interior with N2 to minimize the amount of
air leakage. For details, contact your local Johnson Controls service center.
NOTE: Do not simply drain the chilled/hot, and the cooling water and store the ma-
chine. This significantly increases the possibility of corrosion of the heat transfer tube
and rust.
Содержание YHAU-CGH
Страница 14: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 14 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 38: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 38 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 55: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 JOHNSON CONTROLS 55 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 57: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 57 LD27463...
Страница 59: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 59 LD27465...
Страница 61: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 61 LD27471...
Страница 63: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 63...
Страница 65: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 65 LD27477...
Страница 67: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 67 LD27479...
Страница 69: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 69 LD27475...
Страница 160: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 160 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 170: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 170 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 172: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 172 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 181: ...FORM 155 32 ICOM2 EN UL APPENDIX 1 CHECKLIST ISSUE DATE 1 10 2018 JOHNSON CONTROLS 181 NOTES...