FORM 155.32-ICOM2.EN.UL
SECTION 6 – OPERATION
ISSUE DATE:1/10/2018
JOHNSON CONTROLS
117
Use Simultaneous Residential Hot Water Supply Mode (Option) for Chillers
with Evaporator Heating
In this mode, residential hot water is supplied through the auxiliary heat exchanger (option)
while chilled water or hot water is supplied through the evaporator.
1. Check that the correct Operation Mode button (
Cooling
or
Heating
) is pressed on the
Setting screen. See
2. Press the Simultaneous
ON
button on the Setting screen. See
3. Press the RHW only operation
OFF
button on the Setting screen.
4. Set each Cooling or Heating changeover valve and manual valve to the desired opera-
tion mode (“Simultaneous cooling and residential hot water supply” mode or “Simulta-
neous heating and residential hot water supply” mode). See
Changeover to Residential Hot Water Sole Supply Mode (Option) for Chillers
with Evaporator Heating
In this mode, residential hot water is supplied through the auxiliary heat exchanger (option),
No chilled/hot water is supplied through the evaporator.
1. Choose how to treat the cooling water in the absorber and condenser tubes during the
residential hot water supply operation period. See
Storage Method of the Cooling Wa-
ter During Heating Operation Period on page 153
, for more information and instruc-
tions.
2. Choose how to treat the chilled/hot water in the evaporator tubes during the residen-
tial hot water supply operation period. See
Storage Method of the Cooling Water
During Heating Operation Period on page 153
,
for more information and instructions.
3. Verify the following two manual valves are open:
a. on the weak solution line from the low-temperature heat exchanger to the solution
flow control float valve in the high-temperature generator.
b. on the strong solution line from the high-temperature heat exchanger to the solu-
tion spray pump.
4. Press and hold the Forced Dilution
ON
button on the Setting screen for 10 seconds.
See
5. The solution pump and refrigerant pump start independently.
6. Open the refrigerant manual blow valve. For the location of the blow valve. See
.
The refrigerant in the evaporator is diverted into the absorber.
7. Observe the liquid level at the lower part of the evaporator through the level gauge
(G102).
8. Immediately after the refrigerant liquid level appears in the level gauge (G102), close
the refrigerant manual blow valve (turn it to the right until it stops).
9. Press the Refrigerant Pump
Stop
button on the Setting screen. See
.
10. The refrigerant pump stops. Run the solution pump independently for 10 minutes.
11. Press the Forced Dilution
OFF
button on the Setting screen. See
The solution pump stops.
CAUTION: If you need to change the operation mode, remember to press and hold the
button for 15 seconds.
CAUTION: The chilled/hot water pump should be operating during forced dilution to
prevent freezing of the chilled/hot water.
Содержание YHAU-CGH
Страница 14: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 14 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 38: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 38 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 55: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 JOHNSON CONTROLS 55 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 57: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 57 LD27463...
Страница 59: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 59 LD27465...
Страница 61: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 61 LD27471...
Страница 63: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 63...
Страница 65: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 65 LD27477...
Страница 67: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 67 LD27479...
Страница 69: ...FORM 155 32 ICOM2 EN UL SECTION 4 TECHNICAL DATA ISSUE DATE 1 10 2018 JOHNSON CONTROLS 69 LD27475...
Страница 160: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 160 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 170: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 170 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 172: ...FORM 155 32 ICOM2 EN UL ISSUE DATE 1 10 2018 172 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 181: ...FORM 155 32 ICOM2 EN UL APPENDIX 1 CHECKLIST ISSUE DATE 1 10 2018 JOHNSON CONTROLS 181 NOTES...