<6. PROCEDURES FOR CONVERTER OPERATION>
6-25
IM 12E04A02-02E
The following shows the setting key operations.
(Example of display)
1. Select FUNCTION "C" in the <PROGRAM1>
=> 1.0000
mode.
If the display is only to be confirmed,
operations of 2, 3, and 4 are not necessary.
2. Press the [>] key.
=> 1.0000
The most significant digit flashes.
3. Select a digit with the [>] key and set it to the
=> 1.2000
desired value using the [^] or [v] key.
The flashing digit moves to the right
and when the least significant digit is
reached, it returns to the most
significant digit.
4. Press the [ENT] key to enter the set value.
=> 1.2000
The entire display flashes once.
In step 4, if the set value is beyond the permissible range (0.25 to 4), "not" is displayed.
Reset the message by pressing the [>] key and repeat the operations from step 2.
(11) Setting Detection Level for Spike Detection Function (FUNCTION
“D”)
(Example of display)
1. Select FUNCTION “D” in <PROGRAM1> mode.
=> 00005%
2. Press the [>] key.
=> 0
0005%
The most significant digit flashes.
3. Select a digit with the [>] key and set it to the
=> 0001
0%
desired value using the [^] or [v] key.
The flashing digit moves to the right
and when the least significant digit is
reached, it returns to the most
significant digit.
4. Press the [ENT] key to enter the set value.
=> 00010%
The entire display flashes once.
In step 4, if the set value is beyond the permissible range (1 to 100), "not" is displayed.
Reset the message by pressing the [>] key and repeat the operations from step 2.
(12) Setting Hold Time for Spike Detection Function (FUNCTION “E”)
(Example of display)
1. Select FUNCTION “D” in <PROGRAM1> mode.
=> 00030
2. Press the [>] key.
=> 0
0030
The most significant digit flashes.
3. Select a digit with the [>] key and set it to the
=> 000
5
0
desired value using the [^] or [v] key.
The flashing digit moves to the right
and when the least significant digit is
reached, it returns to the most
significant digit.
4. Press the [ENT] key to enter the set value.
=> 00050
The entire display flashes once.
In step 4, if the set value is beyond the permissible range (1 to 600), "not" is displayed.
Reset the message by pressing the [>] key and repeat the operations from step 2.
3rd Edition : May. 31, 2010-00