18-31
IM 05P02D41-01EN
Parameters
18
Display Function Setting Menu (Menu: DISP) (Continued from previous page)
Parameter
symbol
Name
Display
level
Setting range
Initial
value
HOME
Home Operation
Display setting
PRO
SP1: SP Display
OUT1: OUT Display
HCO: Heating/cooling OUT Display
VP: Valve Position Display
MV: Position Proportional Computation Output
Display
PID1: PID Number Display
HC1: Heater Break Alarm-1 Current Display
HC2: Heater Break Alarm-2 Current Display
PV: PV Analog Input Display
CS1 to CS5: SELECT Display 1 to 5
TSP: TSP Display
R.TIM: Remaining Segment-tim Display
SEG.N: Segment Number Dispaly
R.CYC: Remaining Repetition Display
PTN: Program Pattern Display
SP1
ECO
Economy mode
STD
OFF: Disable
1: Economy mode ON (All indications
except PV display OFF)
2: Economy mode ON (All indications
OFF)
3: Brightness 10 % (All indications)
OFF
BRI
Brightness
EASY
(Dark) 1 to 5 (Bright)
3
B.PVW
White brightness
adjustment of PV
display
PRO
Adjusts the white brightness of PV
display.
(Dark) -4 to 4 (Bright)
0
B.PVR
Red brightness
adjustment of PV
display
PRO
Adjusts the red brightness of PV display.
(Dark) -4 to 4 (Bright)
0
B.SP
Brightness
adjustment of
Setpoint display
PRO
Adjusts the brightness of SP display.
(Dark) -4 to 4 (Bright)
0
B.BAR
Brightness
adjustment of Bar-
graph display
PRO
Adjusts the brightness of SP display.
(Dark) -4 to 4 (Bright)
0
B.STS
Brightness
adjustment of
Status indicator
PRO
Adjusts the brightness of Status indicator.
(Dark) -4 to 4 (Bright)
0
D.CYC
Display update
cycle
PRO
1: 100 ms
2: 200 ms
3: 500 ms
4: 1 s
5: 2 s
2
OP.JP
Autoreturn to
operation display
PRO
Automatically returned to the Operation
Display when there has been no
keystroke operation for 5 minutes.
OFF, ON
ON
MLSD
Least significant
digital mask of PV
display
STD
OFF: With least significant digit
ON: Without least significant digit
OFF
MKTP
Method for least
significant digital
mask of PV display
STD
0: Rounding, 1: Rounding-off
0
SELECT Display Setting Menu (Menu: CSEL)
Parameter
symbol
Name
Display
level
Setting range
Initial value
CS1 to CS5
SELECT Display-1
to -5registration
STD
OFF, 2201 to 5000, 6701 to 6710 OFF
CS10 to
CS19
SELECT
parameter-10 to -19
registration
PRO
OFF, 2201 to 5000
OFF
18.2 List of Parameters
Содержание UP35A
Страница 3: ......
Страница 15: ...Blank Page...
Страница 35: ...Blank Page...
Страница 37: ...Blank Page...
Страница 47: ...Blank Page...
Страница 229: ...Blank Page...
Страница 251: ...Blank Page...
Страница 317: ...Blank Page...
Страница 387: ...Blank Page...
Страница 409: ...Blank Page...
Страница 411: ...Blank Page...