6-28
IM 05P02D41-01EN
Switch
Output action
PROG→RESET
The control output bumps.
RESET→PROG
RESET→LOCAL
The control output does not bump (bumpless).
Output
Control output
Preset output
PROG → RESET RESET → PROG
►
Preset output value: 10.12.1 Setting Output Value in STOP Mode (Preset Output)
The PV event and time event are disabled in RESET mode (OFF).
Operation Display in RESET and RUN Modes
The preset output value is displayed in RESET mode.
When the zone PID selection parameter (ZON) is set to segment PID selection, the
preset output value for the PID group number 1 is output. When the zone PID selection
parameter (ZON) is set to other than segment PID selection, the preset output value
for the PID group number for which zone control is performed is output. And when the
zone PID selection parameter (ZON) is set to the PID number selection for local-mode
operation, the PID parameter is selected by the PID number which is specified in the
parameter L.PID (Local PID number selection).
Operation Display in RESET and PROG Modes in Heating/cooling Control
In RESET mode in Heating/cooling control, the display is as follows. The cooling-side
preset output is displayed on the left and heating-side preset output is displayed on the
right.
Lamp Status
Status
RST lamp
Operation start (PROG)
Unlit
Operation Stop (RESET)
Lit
6.6 Switching Operation Modes
Содержание UP35A
Страница 3: ......
Страница 15: ...Blank Page...
Страница 35: ...Blank Page...
Страница 37: ...Blank Page...
Страница 47: ...Blank Page...
Страница 229: ...Blank Page...
Страница 251: ...Blank Page...
Страница 317: ...Blank Page...
Страница 387: ...Blank Page...
Страница 409: ...Blank Page...
Страница 411: ...Blank Page...