18-34
IM 05P02D41-01EN
DI Function Registration Menu (Menu: DI.SL)
Parameter
symbol
Name
Display
level
Setting range
Initial value
PRG
Switch to PROG (Start of
program operation)
STD
Set an I relay number of
contact input.
Set “OFF” to disable the
function.
Standard terminals
DI1: 5025, DI2: 5026,
DI3: 5027
E1-terminal area
DI11: 5041, DI12: 5042,
DI13: 5043, DI14: 5044,
DI15: 5045
E4-terminal area
DI41: 5089, DI42: 5090,
DI43: 5091, DI44: 5092,
DI45: 5093
5025
RST
Switch to RESET (Stop
of program operation)
STD
5026
LOC
Switch to LOCAL(LSP)
(Start of local-mode
operation)
STD
5027
P/R
PROG/RESET Switch
STD
OFF
P/H
PROG/HOLD Switch
STD
OFF
P/L
PROG/LOCAL(LSP)
Switch
STD
OFF
HOLD
Switch to HOLD (Start of
hold-mode operation)
STD
OFF
ADV
Advance of segment
STD
OFF
WAIT
Wait ON/OFF switch
STD
OFF
S.HLD
Switch to HOLD for
synchronized program
operation
PRO
OFF
A/M
AUTO/MAN switch
STD
OFF
AT
Auto-tuning START/
STOP switch
STD
OFF
LAT
Latch release
STD
OFF
LCD
LCD backlight ON/OFF
switch
STD
OFF
PVRW
PV red/white switch
STD
OFF
P1ST
Prog/reset switch of
program pattern-1
STD
OFF
P2ST
Prog/reset switch of
program pattern-2
STD
OFF
P3ST
Prog/reset switch of
program pattern-3
STD
OFF
P4ST
Prog/reset switch of
program pattern-4
STD
OFF
MG1
Message display
interruption 1
PRO
OFF
MG2
Message display
interruption 2
PRO
OFF
MG3
Message display
interruption 3
PRO
OFF
MG4
Message display
interruption 4
PRO
OFF
18.2 List of Parameters
Содержание UP35A
Страница 3: ......
Страница 15: ...Blank Page...
Страница 35: ...Blank Page...
Страница 37: ...Blank Page...
Страница 47: ...Blank Page...
Страница 229: ...Blank Page...
Страница 251: ...Blank Page...
Страница 317: ...Blank Page...
Страница 387: ...Blank Page...
Страница 409: ...Blank Page...
Страница 411: ...Blank Page...