18-17
IM 05P02D41-01EN
Parameters
18
PID Setting Menu (Menu: PID) (Continued from previous page)
Parameter
symbol
Name
Display
level
Setting range
Initial value
Pc
Cooling-side
proportional band
EASY
0.0 to 999.9%
(Cooling-side ON/OFF control
applies when 0.0% in Heating/
cooling control)
5.0%
Ic
Cooling-side
integral time
EASY
OFF: Disable
1 to 6000 s
240 s
Dc
Cooling-side
derivative time
EASY
OFF: Disable
1 to 6000 s
60 s
OHc
Cooling-side control
output high limit
EASY
0.1 to 105.0%, (OLc<OHc)
100.0%
OLc
Cooling-side control
output low limit
EASY
0.0 to 104.9%, (OLc<OHc)
0.0%
HYSc
Cooling-side
ON/OFF control
hysteresis
EASY
0.0 to 100.0%
0.5%
DB
Output dead band
(in Heating/cooling
control or Position
proportional control)
EASY
In Heating/cooling control: -100.0
to 50.0%
In Position proportional control: 1.0
to 10.0%
3.0%
PO
Preset output
Heating-side preset
output (in Heating/
cooling control)
EASY
-5.0 to 105.0%
In RESET mode, fixed control
output can be generated. In
Position proportional control, Valve
opening can be set
0.0%
POc
Cooling-side preset
output
EASY
-5.0 to 105.0%
In RESET mode, cooling-side fixed
control output can be generated.
0.0%
18.2 List of Parameters
Содержание UP35A
Страница 3: ......
Страница 15: ...Blank Page...
Страница 35: ...Blank Page...
Страница 37: ...Blank Page...
Страница 47: ...Blank Page...
Страница 229: ...Blank Page...
Страница 251: ...Blank Page...
Страница 317: ...Blank Page...
Страница 387: ...Blank Page...
Страница 409: ...Blank Page...