17-11
IM 05P02D41-01EN
Installation and W
iring
17
17.4.5 Contact Input Wiring
CAUTION
1) Use a no-voltage contact (relay contact etc.) for external contacts.
2) Use a no-voltage contact which has ample switching capacity for the terminal's
OFF voltage (approx. 5V) and ON current (approx 1mA).
3) When using a transistor contact, the voltage at both terminals must be 2 V or
less when the contact is ON and the leakage current must be 100 µA or less
when it is OFF.
4) If there is a risk of external lightning surges, use a lightning arrester etc.
Contact Input Equipped as Standard (UP35A/UP32A)
No-voltage contact
Transistor contact
DI3
DI2
DI1
COM
209
210
211
212
DI
Contact rating: 12 V DC, 10 mA or more
DI3
DI2
DI1
COM
209
210
211
212
DI
+
+
+
–
+5 V
+5 V
+5 V
Contact rating: 12 V DC, 10 mA or more
Additional Contact Input According to the UP35A Suffix Codes
(For Detailed model) UP35A Suffix code of Output 2 = “1”
(For Detailed model) UP35A Optional suffix code: /X4
No-voltage contact
Transistor contact
DI41
DI42
DI43
DI44
DI45
COM
Contact rating: 12 V DC, 10 mA or more
501
502
503
504
505
506
DI
DI41
DI42
COM
DI43
DI44
DI45
501
502
503
504
505
506
DI
+5 V
+5 V
+5 V
+5 V
+5 V
Contact rating: 12 V DC, 10 mA or more
+
+
+
+
+
–
17.4 Wiring
Содержание UP35A
Страница 3: ......
Страница 15: ...Blank Page...
Страница 35: ...Blank Page...
Страница 37: ...Blank Page...
Страница 47: ...Blank Page...
Страница 229: ...Blank Page...
Страница 251: ...Blank Page...
Страница 317: ...Blank Page...
Страница 387: ...Blank Page...
Страница 409: ...Blank Page...
Страница 411: ...Blank Page...