• Operation when the measured input does not attain the wait zone within the wait
time
If the wait time elapses before the measured input attains the wait zone, the wait state
is changed to the operating state and the program advances to the next segment the
moment that the wait time elapses. This happens even if the measured input has not
attained the wait zone.
Time
Wait time
Upper-side wait zone
Lower-side wait zone
Wait operation
Though PV has not attained the wait zone,
the program advances to the next segment
the moment that the wait time elapses.
PV
TSP
If the wait time is OFF (No function), the controller keeps the wait status until PV has
attained the wait zone.
9.4 Setting the Wait Functions