17-28
IM 05P02D41-01EN
UP32A
Multiple wiring (multi-drop) of connector
Multiple wiring of the UTAdvanced connector with other devices is possible within
the following multi-wire connection capacity range.
Multi-wire connection capacity (Two wires with the same cross-sectional area)
• Single wire 0.2 to 1.0 mm
2
/twisted wire 0.2 to 1.5 mm
2
• Twisted wire with bar terminal (without plastic sleeve) 0.25 to 1.0 mm
2
• Twisted wire with twin bar terminals (with plastic sleeve) 0.5 to 1.5 mm
2
(
Suffix code 3=3
)
FG: Flame ground
SLD: Shield
DG: TX/RX signal ground
DB: RX/TX signal - signal
DA: RX/TX signal
CHK(red)
(Lit: User profile error/Adress error, Unlit: Normal
)
L ERR(red)
(Lit: Communication failure(CRC error), Unlit: Normal
)
L RUN(green)
(Lit: Normal, Unlit: No carrier detected/Communication timeout)
Not used
CC-L
RS-485
RSB(+)
RSA(-)
SG
If the UP is located at the end of a
segment for the CC-Link
communication wiring,terminating
resistors are separately needed.
These are to be prepared by users.
(110 Ω: 1 pc.)
DB
DA
110Ω
301
302
303
304
305
306
307
308
309
310
311
312
Up to 32 UTAdvanced series
(
Modbus/RTU
slave
)
controllers can be connected.
Note
Use FG as an exclusive ground. Be sure to ground using a low grounding resistance.
Modbus master wiring
RS-485 communication wiring for the serial gateway function is as follows.
Up to 32 UTAdvanced series controllers can be connected.
17.4 Wiring
Содержание UP35A
Страница 3: ......
Страница 15: ...Blank Page...
Страница 35: ...Blank Page...
Страница 37: ...Blank Page...
Страница 47: ...Blank Page...
Страница 229: ...Blank Page...
Страница 251: ...Blank Page...
Страница 317: ...Blank Page...
Страница 387: ...Blank Page...
Страница 409: ...Blank Page...
Страница 411: ...Blank Page...