Description
Auto-tuning is a function with which the controller automatically measures the process
characteristics and sets PID constants, which are control-related parameters, to optimum
values for the setpoint. Auto-tuning temporarily executes ON/OFF control, calculates
appropriate PID constants from response data obtained, and sets these constants.
CAUTION
Do not perform auto-tuning for the following processes.
Tune PID manually.
● Processes with fast response such as flow rate control and pressure control.
● Processes which do not allow the output to be turned on and off even
temporarily.
● Processes which prohibit output changes at control valves (or other actuators).
● Processes in which product quality can be adversely affected if PV values
fluctuate beyond their allowable ranges.
AT = Started
ON
OFF
Temperature
SP
Control
output
Time
ON/OFF control
PID control using PID
constants calculated from
the AT results
Auto-tuning in progress
MAN lamp blinkng
There is a hysteresis of 0.25% of the input range above and below SP.
When SP bias in auto-tuning is set
AT = Started
ON
OFF
Temperature
SP+AT.BS
SP
Control
output
Time
ON/OFF control
SP bias in auto-tuning
(negative setpoint)
PID control using PID
constants calculated from
the AT results
Auto-tuning in progress
MAN lamp blinkng
There is a hysteresis of 0.25% of the input range above and below SP.
6.2 Performing and Canceling Auto-tuning
Содержание UP35A
Страница 3: ......
Страница 15: ...Blank Page...
Страница 35: ...Blank Page...
Страница 37: ...Blank Page...
Страница 47: ...Blank Page...
Страница 229: ...Blank Page...
Страница 251: ...Blank Page...
Страница 317: ...Blank Page...
Страница 387: ...Blank Page...
Страница 409: ...Blank Page...
Страница 411: ...Blank Page...