8-29
IM 05P02D41-01EN
Control Functions
Example of Overshoot Suppression Control for Setpoint Changes
Time
Time
Temperature
Temperature
SUPER is not used
SUPER is used
Example of Overshoot Suppression Control for Ramp-to-soak Transition
SUPER is not used
SUPER is used
Time
Time
Sub-SP
Temperature
Temperature
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
SC
Super function
EASY
OFF: Disable
1: Overshoot suppressing function
(normal mode)
2: Hunting suppressing function
(stable mode)
3: Hunting suppressing function
(response mode)
4: Overshoot suppressing function
(strong suppressing mode)
TUNE
The setting SC=4 is effective compared with SC=1. However, the hunting may occur until
the PV reaches SP. Use it as usage.
8
8.5 Suppressing Overshoot (Super Function)