vii
IM 05P02D41-01EN
Model and Suffix Codes of UP35A (for Detailed Code Model)
Model
Suffix code
Optional
suffix
code
Description
UP35A
Program Controller (provided with 3 DIs, and 3 DOs) (Power supply:
100-240 V AC)
2 program patterns/20 program segments (Max. 20 segments per pattern)
Fixed code
-NNN
Always “-NNN”
Display language (*1)
-1
English (Default. Can be switched to other language by the setting.)
-2
German (Default. Can be switched to other language by the setting.)
-3
French (Default. Can be switched to other language by the setting.)
-4
Spanish (Default. Can be switched to other language by the setting.)
Case color
0
White (Light gray)
1
Black (Light Charcoal gray)
Output 1 (*2) (*3) (*5)
-A
Analog output (current/voltage pulse)
-R
Relay output (c-contact)
-U
Universal output (current/voltage pulse/relay)
-T
Triac output
-P
Position proportional output
Output 2 (*2) (*3) (*4) (*5)
A
Analog output (current/voltage pulse)
R
Relay output (a-contact)
U
Universal output (current/voltage pulse/relay)
N
None
Additional program pattern
/AP
2 additional patterns/20 additional segments
Retransmission output (*4)
/RT
Retransmission output or 15 V DC power supply
Heater break alarm (*5)
/HA
Heater break alarm
E1 terminal area (*6)
/X1
5 additional DIs
/Y1
5 additional DOs
/W1
2 additional DIs and 2 additional DOs
E3 terminal area (*6) (*7)
/CH3
RS485 communication (Max. 38.4 kbps, 2-wire/4-wire)
/CC3
CC-Link communication (with Modbus master function)
/PD3
PROFIBUS-DP communication (with Modbus master function)
/DN3
DeviceNet communication (with Modbus master function)
/ET3
Ethernet communication (with serial gateway function)
E4 terminal area (*6) (*7)
/L4
24 V DC loop power supply
/X4
5 additional DIs
/Y4
5 additional DOs
/W4
2 additional DIs and 2 additional DOs
Power supply
/DC
Power supply 24 V AC/DC
Additional treatment (*8)
/CT
Coating
*1:
English, German, French, and Spanish are available for the guide display.
*2:
For heating/cooling output, both Output 1 and Output 2 should be specified. Not available
when Output 2 is “N”. For position proportional output, specify “-P” for Output 1 and “N” for
Output 2.
*3:
When the code for Output 1 is "-R" or "-U" and Output 2 is "R" or "U", Output 1 is changed
from the contact point c to the contact point a. When the code for Output 1 is specified to
"-T", only "A" or "N" is available for Output 2.
*4:
The /RT option can be specified only when the code for Output 2 is “R” or “N.”
*5:
The /HA option can be specified in the combination of Output 1 and Output 2 codes except
for “-PN.”
*6:
Only one option is available for each terminal area of E1, E2 and E4.
*7:
The /L4 option for E4 terminal area can be specified only when the E3 terminal area option
is not specified or specified /CH3.
*8:
When the /CT option is specified, the UP35A does not conform to the safety standards (UL
and CSA) and CE marking (Products with /CT option are not intended for EEA-market).
Содержание UP35A
Страница 3: ......
Страница 15: ...Blank Page...
Страница 35: ...Blank Page...
Страница 37: ...Blank Page...
Страница 47: ...Blank Page...
Страница 229: ...Blank Page...
Страница 251: ...Blank Page...
Страница 317: ...Blank Page...
Страница 387: ...Blank Page...
Страница 409: ...Blank Page...
Страница 411: ...Blank Page...