9-11
IM 05P02D41-01EN
Program Pattern Functions
9
PV at start
Operation-starting point
a
A1
b
B1
c
C1
d
D1
e
E1 (SSP)
Example of programs with only ramp-up segments
The program pattern contains points A1 to E1.
For some PV, the program advances through the segments up to the point at which the
ramp is reversed.
When the program operation starting point is set to A1, program operation is performed
for one control period, and program operation ends according to the junction code (JC)
for segment 2.
D1
E1
B1
C1
TSP
SSP
Segment 1
Segment 2
a
b
c
d
e
A1
Program pattern
Program operation start (PRG)
Time
Setpoint
PV at start
Operation-starting point
a
A1
b
B1
c
C1
d
D1
e
E1 (SSP)
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
SSP
Starting target
setpoint
EASY
0.0 to 100.0% of PV input range
(EU)
(Setting range: P.RL to P.RH)
PROG
STC
Start code
EASY
SSP: Program operation begins
with the starting target setpoint.
RAMP: Ramp-prioritized PV start
TIME: Time-prioritized PV start
LSP: Local-mode start
9.3 Setting the Program Starting Conditions (STC)