6-13
IM 05P02D41-01EN
Monitoring and Control of Regular Operations
6
6.2 Performing and Canceling Auto-tuning
Setting Display
Operation Mode Setting Display
Operation Display >
PARAMETER
key or
PARA
key for
3 seconds
(to [
MODE
] Menu Display) >
SET/ENTER
key
(The operation mode is displayed.) >
Down arrow
key (The
operation mode is displayed.)
The parameter AT is displayed when the operation mode is
AUTO.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
AT
AUTO-tuning
switch
EASY
OFF: Disable
1: Perform auto-tuning. Tuning
result is stored in the PID of
group 1.
2: Perform auto-tuning. Tuning
result is stored in the PID of
group 2.
3: Perform auto-tuning. Tuning
result is stored in the PID of
group 3.
4: Perform auto-tuning. Tuning
result is stored in the PID of
group 4.
R: Tuning result is stored in the PID
for reference deviation.
MODE
AT.BS
SP bias in auto-
tuning
PRO
-100.0 to 100.0% of PV input range
span (EUS)
TUNE
CAUTION
Set the operation mode to AUTO and PRG/LOC to perform auto-tuning.
Lamp Status
Status
STOP lamp
MAN lamp
During auto-tuning
Unlit
Blinking
Содержание UP35A