AL1-AL3 Function Registration Menu (Menu: ALM)
Parameter
symbol
Name
Display
level
Setting range
Initial value
AL1.S
AL1 function
selection
STD
Set an I relay number.
Setting range: 4001 to 6304
No function: OFF
PV event 1: 4801,
PV event 2: 4802,
Time event 1: 4817,
Time event 2: 4818,
Time event 3: 4819,
Time event 4: 4821,
Alarm 1: 4353,
Alarm 2: 4354,
AUTO (OFF) / MAN (ON) status: 4177,
Program RESET status: 4181,
Program RUN status: 4182,
Local operation status: 4183,
HOLD mode status: 4189,
Program advance status: 4187,
Pattern end signal (1 second): 4265,
Pattern end signal (3 seconds): 4266,
Pattern end signal (5 seconds): 4267,
Wait end signal (1 second) : 4257,
Wait end signal (3 seconds) : 4258,
Wait end signal (5 seconds) : 4259,
FAIL (Normally ON) output: 4256
4801
AL2.S
AL2 function
selection
STD
4802
AL3.S
AL3 function
selection
STD
4817
OR.S
OUT relay function
selection
STD
OFF
OR2.S
OUT2 relay function
selection
STD
OFF
AL1.D
AL1 contact type
PRO
0: When the event of assigned
function occurs, the contact
output is closed.
1: When the event of assigned
function occurs, the contact
output is opened.
0
AL2.D
AL2 contact type
PRO
0
AL3.D
AL3 contact type
PRO
0
OR.D
OUT relay contact
type
PRO
0
OR2.D
OUT2 relay contact
type
PRO
0
18.2 List of Parameters
Содержание UP35A
Страница 3: ......
Страница 15: ...Blank Page...
Страница 35: ...Blank Page...
Страница 37: ...Blank Page...
Страница 47: ...Blank Page...
Страница 229: ...Blank Page...
Страница 251: ...Blank Page...
Страница 317: ...Blank Page...
Страница 387: ...Blank Page...
Страница 409: ...Blank Page...
Страница 411: ...Blank Page...