13-13
IM 05P02D41-01EN
Display
, Key
, and Security Functions
13.1.10
Setting Message Function
Description
Using the message function and turning the contact input on/off, the message registered
beforehand can be displayed on PV display by interrupt.
The message is registered using LL50A Parameter Setting Software.
The messages are limited to 20 alphanumeric characters. A maximum of four messages
can be registered.
If a number of messages occur simultaneously, the priority is as follows:
(high) MG1>MG2>MG3>MG4 (low)
► Message registration: LL50A Parameter Setting Software User’s Manual
►
Registration of contact input: 12.1.1 Setting Contact Input Function
►
Registration symbols: 3.3 List of Display Symbols
When the contact input is
turned on, the scrolling
message registered
beforehand is displayed
on PV Display.
Operation Display
13.1.11
Switching Guide Display Language
Description
The guide display language that appears when the parameter or the menu is displayed
can be switched.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
LANG
Guide display
language
EASY
ENG: English
FRA: French
GER: German
SPA: Spanish
SYS
13
13.1 Setting Display Functions
Содержание UP35A
Страница 3: ......
Страница 15: ...Blank Page...
Страница 35: ...Blank Page...
Страница 37: ...Blank Page...
Страница 47: ...Blank Page...
Страница 229: ...Blank Page...
Страница 251: ...Blank Page...
Страница 317: ...Blank Page...
Страница 387: ...Blank Page...
Страница 409: ...Blank Page...
Страница 411: ...Blank Page...