18-9
IM 05P02D41-01EN
Parameters
18
SELECT Parameter Menu (Menu: CS)
Parameter
symbol
Name
Display
level
Setting range
Initial value
CS10 to
CS19
SELECT parameter
10 to 19
EASY
Setting range of a registered
parameter.
-
Program Pattern Setting Menu (Menu: PROG>PTNO. (=01 to 02 (04 when the option
“/AP” is specified.)) > SEGNO. (=00))
Parameter
symbol
Name
Display
level
Setting range
Initial value
SSP
Starting target
setpoint
EASY
0.0 to 100.0% of PV input range
(EU) (Setting range: P.RL to P.RH) P.RL
STC
Start code
EASY
SSP: Program operation begins
with the starting target setpoint.
RAMP: Ramp-prioritized PV start
TIME: Time-prioritized PV start
LSP: Local-mode start
* STC=TIME cannot be selected
when the parameter SEG.T is
TM.RT.
SSP
WT.SW
Wait function ON/
OFF
STD
OFF: Disable
ON: Enable
OFF
WZ.UP
Upper-side wait
zone
STD
0.0 to 10.0% of PV input range (EU)
0.5% of PV
input range
WZ.LO
Lower-side wait
zone
STD
0.5% of PV
input range
WT.TM
Wait time
STD
OFF: No function
0.00 to 999.59 (“hour.minute” or
“minute.second”)
* Available only for the wait time
at the segment switching.
* Use the parameter TMU to set
the time unit. (Common in the
instrument.)
OFF
R.CYCL
Number of repeat
cycles
STD
0 to 999, CONT (The controller
indefinitely repeats the segment
specified by the R.STRT and
R.END parameters.)
0
R.STRT
Repeat cycle start
segment number
STD
1 to 20 (40 when the option “/AP”
is specified.)
1 ≤ R.STRT ≤ R.END ≤ 20 (40)
1
R.END
Repeat cycle end
segment number
STD
1
18.2 List of Parameters
Содержание UP35A
Страница 3: ......
Страница 15: ...Blank Page...
Страница 35: ...Blank Page...
Страница 37: ...Blank Page...
Страница 47: ...Blank Page...
Страница 229: ...Blank Page...
Страница 251: ...Blank Page...
Страница 317: ...Blank Page...
Страница 387: ...Blank Page...
Страница 409: ...Blank Page...
Страница 411: ...Blank Page...