2-10
IM CW240E
●
Indications on the basis of other input conditions
Measurement Item
Electric energy
Reactive energy
Power factor
Power factor demand
Total power factor
Phase angle
Power phase angle
Reactive power
Apparent power
Conditions and Indications
• When the display setting is any item other than AUTO, if the
integrated value exceeds "999999", the reading is reset to
"0", letting integration continue.
• When the display setting is AUTO, the position of a decimal
point or the unit of measurement is shifted by one digit to
continue integration.
Because of a computation error, if the power factor:
• Exceeds 1.0, the reading becomes "1.0."
• Is less than -1.0, the reading becomes "-1.0."
• Is S < |P|, the reading becomes "1.0."
Because of a computation error, if the power factor:
• Exceeds 1.0, the reading becomes "1.0."
• Is less than -1.0, the reading becomes "-1.0."
If the power factor exceeds 1.0 or is less than -1.0 due to a
computation error, the reading becomes "0
°
."
If the total power factor exceeds 1.0 or is less than -1.0 due to
a computation error, the reading becomes "0
°
."
Because of a computation error, if
• A value in is negative, the reading becomes "0."
• S < |P|, the reading becomes "0."
If S < |P| due to a computation error, S = |P|.
Legend
P : active power value
S : apparent power value
2.5 Overrange/Error Indication during Measurement