V-Protection Module – Voltage Protection [27/59]
Parameter
Description
Setting range
Default
Menu path
V(t)<2
Pick-up value
Only available if: Device
planning: V.Mode =
V(t)<
0.01 - 2.00Vn
0.01Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
t2
Tripping delay
Only available if: Device
planning: V.Mode =
V(t)<
0.00 - 10.00s
0.15s
[Protection Para
/<n>
/V-Prot
/V[1]]
V(t)<3
Pick-up value
Only available if: Device
planning: V.Mode =
V(t)<
0.01 - 2.00Vn
V[1]: 0.70Vn
V[2]: 0.70Vn
V[3]: 0.70Vn
V[4]: 0.30Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
t3
Tripping delay
Only available if: Device
planning: V.Mode =
V(t)<
0.00 - 10.00s
0.15s
[Protection Para
/<n>
/V-Prot
/V[1]]
V(t)<4
Pick-up value
Only available if: Device
planning: V.Mode =
V(t)<
0.01 - 2.00Vn
V[1]: 0.70Vn
V[2]: 0.70Vn
V[3]: 0.70Vn
V[4]: 0.30Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
t4
Tripping delay
Only available if: Device
planning: V.Mode =
V(t)<
0.00 - 10.00s
V[1]: 0.70s
V[2]: 0.70s
V[3]: 0.70s
V[4]: 0.6s
[Protection Para
/<n>
/V-Prot
/V[1]]
V(t)<5
Pick-up value
Only available if: Device
planning: V.Mode =
V(t)<
0.01 - 2.00Vn
0.90Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
t5
Tripping delay
Only available if: Device
planning: V.Mode =
V(t)<
0.00 - 10.00s
1.50s
[Protection Para
/<n>
/V-Prot
/V[1]]
V(t)<6
Pick-up value
Only available if: Device
planning: V.Mode =
V(t)<
0.01 - 2.00Vn
0.90Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
EN MRU4 10/09
Page 241
Содержание HighPROTEC MRU4
Страница 1: ...MRU4 HighPROTEC Voltage Frequency Protection Device Manual DOK HB MRU4E...
Страница 3: ...Order Code EN MRU4 10 09 Page 3...
Страница 43: ...Navigation Operation Navigation Operation EN MRU4 10 09 Page 43 1 2 3 5 7 6 8 9...
Страница 307: ...Service Service General Within this menu you can initiate a reboot of the device EN MRU4 10 09 Page 307...