Blockings
Blockings
The device provides a function for temporary and permanent blocking of the complete protection functionality or
of single protection stages.
Make absolutely sure that no illogical or even life-threatening blockings are
allocated.
Make sure that you do not carelessly deactivate protection functions which
have to be available according to the protection concept.
Permanent Blocking
Switching ON or OFF the complete protection functionality
In module
»Protection«
the complete protection of the device can be switched on or off. Set the parameter
Function
to
»active«
or
»inactive«
in module
»Prot«
.
Only if in module »Prot« the parameter
»Function«
is =
»active«
, the
protection is activated; i.e. with
»Function«
=
»inactive«,
no protection
function is operating. Then the device cannot protect any components.
Switching modules ON or OFF
Each of the modules can be switched on or off (permanently). This is achieved when the parameter »
Function«
is set to »active« or »inactive« in the respective module.
Activating or deactivating the tripping command of a protection stage permanently
In each of the protection stages the tripping command to the CB can be permanently blocked. For this purpose
the parameter
»TripCmd Blo«
has to be set to
»active«
.
Temporary Blocking
To block the complete protection of the device temporarily by a signal
In module
»Prot«
the complete protection of the device can be blocked temporarily by a signal. On condition that
a module-external blocking is permitted
»ExBlo Fc=active«
. In addition to this, a related blocking signal from the
»assignment list« must have been assigned. For the time the allocated blocking signal is active, the module is
blocked.
If the module
»Prot«
is blocked, the complete protection function does not
work. As long as the blocking signal is active, the device cannot protect
any components.
To block a complete protection module temporarily by an active assignment
•
In order to establish a temporary blockage of a protection module, the parameter
»ExBlo Fc«
of the
module has to be set to
»active«
. This gives the permission: »This module can be blocked«.
•
Within the general protection parameters a signal has to be additionally chosen from the »
ASSIGNMENT
LIST
«. The blocking only becomes active when the assigned signal is active.
Page 212
EN MRU4 10/09
Содержание HighPROTEC MRU4
Страница 1: ...MRU4 HighPROTEC Voltage Frequency Protection Device Manual DOK HB MRU4E...
Страница 3: ...Order Code EN MRU4 10 09 Page 3...
Страница 43: ...Navigation Operation Navigation Operation EN MRU4 10 09 Page 43 1 2 3 5 7 6 8 9...
Страница 307: ...Service Service General Within this menu you can initiate a reboot of the device EN MRU4 10 09 Page 307...