f-Protection Module – Frequency [81O/U, 78, 81R]
Parameter
Description
Setting range
Default
Menu path
f<
Pick-up value for
underfrequency.
Only available if: Device
planning: f.Mode = f< Or
f< and df/dt Or f< and DF/
DT
40.00 - 69.95Hz
49.00Hz
[Protection Para
/<n>
/f-Prot
/f[1]]
t
Tripping delay
Only available if: Device
planning: f.Mode = f< Or
f>Or f> and df/dt Or f<
and df/dt
0.00 - 3600.00s
1.00s
[Protection Para
/<n>
/f-Prot
/f[1]]
df/dt
Measured value
(calculated): Rate-of-
frequency-change.
Only available if: Device
planning: f.Mode = df/dt
Or f< and df/dt Or f> and
df/dt
0.1 - 10.0Hz/s
1.0Hz/s
[Protection Para
/<n>
/f-Prot
/f[1]]
t-df/dt
Trip delay df/dt
0.00 - 300.00s
1.00s
[Protection Para
/<n>
/f-Prot
/f[1]]
DF
Frequency difference for
the maximum admissable
variation of the mean of
the rate of frequency-
change. This function is
inactive if DF=0.
Only available if: Device
planning: f.Mode = f<
and DF/DT Or f> and DF/
DT
0.0 - 10.0Hz
1.00Hz
[Protection Para
/<n>
/f-Prot
/f[1]]
DT
Time interval of the
maximum admissable
rate-of-frequency-
change.
Only available if: Device
planning: f.Mode = f<
and DF/DT Or f> and DF/
DT
0.1 - 10.0s
1.00s
[Protection Para
/<n>
/f-Prot
/f[1]]
Page 262
EN MRU4 10/09
Содержание HighPROTEC MRU4
Страница 1: ...MRU4 HighPROTEC Voltage Frequency Protection Device Manual DOK HB MRU4E...
Страница 3: ...Order Code EN MRU4 10 09 Page 3...
Страница 43: ...Navigation Operation Navigation Operation EN MRU4 10 09 Page 43 1 2 3 5 7 6 8 9...
Страница 307: ...Service Service General Within this menu you can initiate a reboot of the device EN MRU4 10 09 Page 307...