VTS-Supervision Module - Voltage Transformer Supervision [60FL]
Commissioning: Voltage Transformer Supervision (via DI) [60FL]
Object to be tested
Check if the auto fuse failure is correctly identified by the device.
Procedure
Disconnect the automatic circuit breaker of the VTs (all poles to be dead)
Successful test result
•
The state of the respective digital input changes.
•
If a LED is allocated to the auto fuse failure, this is indicated accordingly.