Module: Protection (Prot)
Module: Protection (Prot)
Prot
The module
»Protection«
serves as outer frame for all other protection modules, i.e. they are all enclosed by the
module
»Protection«
.
All alarms and tripping commands are combined in module
»Protection«
by an OR-logic.
If in module
»Protection«
the parameter
»Function«
is set on »inactive« or
in case the module is blocked, then the complete protective function of the
device does not work anymore.
Protection inactive
If the master module
»Protection«
was permanently deactivated or if a temporary blockage of this module has
occurred and the allocated blocking signal is still active, then the complete functionality (protection) of the device
is zero. In such a case the protective function is »inactive«.
Protection active
If the master module
»Protection«
was activated and a blockade for this module was not activated respectively
the assigned blocking signal is inactive at that moment, then the
»Protection«
is
»active«
.
EN MRU4 10/09
Page 217