Module: Fault Recorder
Read Out the Fault Recorder
The measured values at the time of tripping are saved (failure safe) within the fault recorder. If there is no more
memory free, the oldest record will be overwritten (FIFO).
In order to read out a failure record:
•
call up the main menu,
•
call up the submenu Operation/Recorders/Fault rec.,
•
select a fault record,
•
analyze the corresponding measured values.
Read Out the Fault Recorder via Smart View
•
In case
Smart view
is not running – please start it.
•
If device data has not been loaded yet – click »Receive Data From The Device« in menu »Device«.
•
Double click the »Operation« icon in the navigation tree.
•
Double click the »Fault Rec« icon within the tree »Operation/Recorders«.
•
In the window the fault recordings are shown in tabular form.
•
In order to receive more detailed information on a fault, click the »Plus Sign« in front of the fault number.
EN MRU4 10/09
Page 151