Binary Output Relays
Global Protection Parameters of the Binary Output Relays
Parameter
Description
Setting range
Default
Menu path
t-hold
To clearly identify the
state transition of a
binary output relay, the
"new state" is being hold,
at least for the duration of
the hold time.
0.00 - 300.00s
0.03s
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Latched
Defines whether the
Binary Output Relay will
be acknowledged
automatically if the event
is gone or whether the
Binary Output Relay is to
be acknowledged by a
signal/manually.
inactive,
active
active
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Acknowledgement
Acknowledgement Signal
- An acknowledgement
signal (that
acknowledges the
corresponding binary
output relay) can be
assigned to each output
relay. The
acknowledgement-signal
is only effective if the
parameter "Latched" is
set to active.
Only available if: Latched
= active
1..n, Assignment List
-
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Inverting
Inverting of the Binary
Output Relay.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Assignment 1
Assignment
1..n, Assignment List
TripCmd
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Inverting 1
Inverting of the state of
the assigned signal.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X2
/BO 1]
Page 102
EN MRU4 10/09
Содержание HighPROTEC MRU4
Страница 1: ...MRU4 HighPROTEC Voltage Frequency Protection Device Manual DOK HB MRU4E...
Страница 3: ...Order Code EN MRU4 10 09 Page 3...
Страница 43: ...Navigation Operation Navigation Operation EN MRU4 10 09 Page 43 1 2 3 5 7 6 8 9...
Страница 307: ...Service Service General Within this menu you can initiate a reboot of the device EN MRU4 10 09 Page 307...