Installation and Connection
Installation and Connection
Three-Side-View
Dependent on the connection method of the SCADA system used the
needed space (depth) differs. If, for instance, a D-Sub-Plug is used, it has to
be added to the depth dimension.
3-Side-View B1 Housing
The housing must be carefully grounded. Connect a ground cable (4 to 6
mm
2
(AWG 12-10) / 1,7 Nm [15 In-lb]) to the housing, using the screw, which
is marked with the ground symbol (at the rear side of the device).
The power supply card needs a separate ground connection (2.5 mm
2
(AWG 14) at terminal X1 (0.56-0.79 Nm [5-7 In-lb]).
EN MRU4 10/09
Page 21