TCS-Supervision Module – Trip Circuit Supervision [74TC]
Setting Group Parameters of the Trip Circuit Supervision Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or
deactivation of
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/Supervision
/TCS]
ExBlo Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parameterized "ExBlo
Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/Supervision
/TCS]
t-TCS
Tripping delay time of the
Trip Circuit Supervision
0.10 - 10.00s
0.2s
[Protection Para
/<n>
/Supervision
/TCS]
Page 286
EN MRU4 10/09