V 012 - Protection Module Asymmetry [47]
Parameter set parameters of the asymmetry module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or
deactivation of
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/V 012 [1]]
ExBlo Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parameterized "ExBlo
Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/V 012 [1]]
Blo TripCmd
Permanent blocking of
the Trip Command of the
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/V 012 [1]]
ExBlo TripCmd Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parameterized "ExBlo
TripCmd Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/V 012 [1]]
V1>
Positive Phase Sequence
Overvoltage
Only available if: Device
planning: V 012.Mode =
V1>
0.01 - 2.00Vn
1.00Vn
[Protection Para
/<n>
/V-Prot
/V 012 [1]]
Page 272
EN MRU4 10/09
Содержание HighPROTEC MRU4
Страница 1: ...MRU4 HighPROTEC Voltage Frequency Protection Device Manual DOK HB MRU4E...
Страница 3: ...Order Code EN MRU4 10 09 Page 3...
Страница 43: ...Navigation Operation Navigation Operation EN MRU4 10 09 Page 43 1 2 3 5 7 6 8 9...
Страница 307: ...Service Service General Within this menu you can initiate a reboot of the device EN MRU4 10 09 Page 307...