V-Protection Module – Voltage Protection [27/59]
Setting Group Parameters of the Voltage Protection Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or
deactivation of
module/stage.
inactive,
active
V[1]: active
V[2]: active
V[3]: inactive
V[4]: inactive
[Protection Para
/<n>
/V-Prot
/V[1]]
ExBlo Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parameterized "ExBlo
Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/V[1]]
Blo TripCmd
Permanent blocking of
the Trip Command of the
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/V[1]]
ExBlo TripCmd Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parameterized "ExBlo
TripCmd Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/V[1]]
Meas Mode
Measuring/Supervision
Mode: Determines if the
phase-to-phase or
phase-to-earth voltages
are to be supervisioned
Phase to Earth,
Phase to Phase
Phase to Earth
[Protection Para
/<n>
/V-Prot
/V[1]]
EN MRU4 10/09
Page 239
Содержание HighPROTEC MRU4
Страница 1: ...MRU4 HighPROTEC Voltage Frequency Protection Device Manual DOK HB MRU4E...
Страница 3: ...Order Code EN MRU4 10 09 Page 3...
Страница 43: ...Navigation Operation Navigation Operation EN MRU4 10 09 Page 43 1 2 3 5 7 6 8 9...
Страница 307: ...Service Service General Within this menu you can initiate a reboot of the device EN MRU4 10 09 Page 307...