Module: Fault Recorder
Module: Fault Recorder
Fault rec
The fault recorder can be started by one of eight start events (selection from the »assignment list«/OR-Logic).
The fault recorder can register up to 20 faults. The last of the recorded faults is stored in a fail-safe manner.
If one of the assigned trigger events becomes true, the fault recorder will be started. Each fault is saved inclusive
module and name, fault number, mains fault number and record number at that time one of the trigger events
becomes true. To each of the faults the measuring values (at the time when the trigger event became true) can
be viewed.
Up to 8 signals to trigger the fault recorder can be selected from the »assignment list«. The trigger events are
OR-linked.
The parameter
»Auto Delete«
defines how the device shall react if there is no saving place available. In case
»Auto Delete«
is
»active«
, the first recorded fault will be overwritten according to the FIFO principle. If the
parameter is set to
»inactive«
, recording of the fault events will be stopped until the storage location is released
manually.
Page 150
EN MRU4 10/09
Start: 1
Trigger
>1
Start: 2
Trigger
Start: 3
Trigger
Start: 4
Trigger
Start: 5
Trigger
Start: 6
Trigger
Start: 7
Trigger
Start: 8
Trigger
Man Trigger
Recording
>1
Содержание HighPROTEC MRU4
Страница 1: ...MRU4 HighPROTEC Voltage Frequency Protection Device Manual DOK HB MRU4E...
Страница 3: ...Order Code EN MRU4 10 09 Page 3...
Страница 43: ...Navigation Operation Navigation Operation EN MRU4 10 09 Page 43 1 2 3 5 7 6 8 9...
Страница 307: ...Service Service General Within this menu you can initiate a reboot of the device EN MRU4 10 09 Page 307...