Module: Modbus® (Modbus)
Parameter
Description
Setting range
Default
Menu path
t-timeout
Within this time the
answer has to be
received by the SCADA
system, otherwise the
request will be
disregarded. In that case
the Scada system
detects a communication
failure and the Scada
System has to send a
new request.
Only available if:Device
planning = RTU
0.01 - 10.00s
1s
[Device Para
/Modbus]
Baud rate
Baud rate
Only available if:Device
planning = RTU
1200,
2400,
4800,
9600,
19200,
38400
19200
[Device Para
/Modbus]
Physical Settings
Digit 1: Number of bits.
Digit 2: E=even parity,
O=odd parity, N=no
parity. Digit 3: Number of
stop bits. More
information on the parity:
It is possible that the last
data bit is followed by a
parity bit which is used
for recognition of
communication errors.
The parity bit ensures
that with even parity
("EVEN") always an even
number of bits with
valence "1" or with odd
parity ("ODD") an odd
number of "1" valence
bits are transmitted. But it
is also possible to
transmit no parity bits
(here the setting is "Parity
= None"). More
information on the stop-
bits: The end of a data
byte is terminated by the
stop-bits.
Only available if:Device
planning = RTU
8E1,
8O1,
8N1,
8N2
8E1
[Device Para
/Modbus]
EN MRU4 10/09
Page 165
Содержание HighPROTEC MRU4
Страница 1: ...MRU4 HighPROTEC Voltage Frequency Protection Device Manual DOK HB MRU4E...
Страница 3: ...Order Code EN MRU4 10 09 Page 3...
Страница 43: ...Navigation Operation Navigation Operation EN MRU4 10 09 Page 43 1 2 3 5 7 6 8 9...
Страница 307: ...Service Service General Within this menu you can initiate a reboot of the device EN MRU4 10 09 Page 307...