TCS-Supervision Module – Trip Circuit Supervision [74TC]
TCS-Supervision Module – Trip Circuit Supervision
[74TC]
TCS
The trip circuit is monitored by evaluating the auxiliary contacts of the circuit breaker. The CB trip circuits
inclusive cable can be monitored by two non-grouped digital inputs. If a circuit is broken an alarm is issued. With
this protection module it is assumed that the CB is provided with auxiliary contacts (CB-open and CB-closed),
allocated to the digital inputs.
In Slot 1 has 2 digital inputs, each of which has a separate root (contact
separation) for the trip circuit supervision.
In this case the trip circuit supply voltage serves also as supply voltage for the digital inputs and so the supply
voltage failure of a trip circuit can be detected directly.
In order to identify a conductor-failure in the trip circuit on the supply line or in the trip coil, the off-coil has to be
looped-in to the supervision circuit.
Via the two digital inputs the auxiliary contacts are checked continuously (»I
NPUT
1« and »Input 2«) for »identity«
(both open or both closed). If »identity« is identified, the trip circuit is checked for a possible defect after a set
time delay and if necessary the »TCS.A
LARM
« is issued.
The time delay is to be set in a way that switching actions cannot cause false trips in this module.
Page 282
EN MRU4 10/09
Содержание HighPROTEC MRU4
Страница 1: ...MRU4 HighPROTEC Voltage Frequency Protection Device Manual DOK HB MRU4E...
Страница 3: ...Order Code EN MRU4 10 09 Page 3...
Страница 43: ...Navigation Operation Navigation Operation EN MRU4 10 09 Page 43 1 2 3 5 7 6 8 9...
Страница 307: ...Service Service General Within this menu you can initiate a reboot of the device EN MRU4 10 09 Page 307...