V-Protection Module – Voltage Protection [27/59]
Parameter
Description
Setting range
Default
Menu path
Alarm Mode
Alarm criterion for the
voltage protection stage.
1-ph Trip,
3-ph Trip
1-ph Trip
[Protection Para
/<n>
/V-Prot
/V[1]]
V>
Pick-up value
Only available if: Device
planning: V.Mode = V>
0.01 - 2.00Vn
V[1]: 1.1Vn
V[2]: 1.20Vn
V[3]: 1.20Vn
V[4]: 1.20Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
V<
Pick-up value
Only available if: Device
planning: V.Mode = V<
Only available if: Device
planning: V.Mode =
V(t)<
0.01 - 2.00Vn
V[1]: 0.80Vn
V[2]: 0.9Vn
V[3]: 0.80Vn
V[4]: 0.80Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
Ex Fuse Fail VT
Blocking if the fuse of a
voltage transformer has
tripped.
Only available if: Device
planning: V.Mode =
V(t)<
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/V[1]]
t
Tripping delay
Only available if: Device
planning: V.Mode = V>
Or V<
0.00 - 300.00s
V[1]: 1s
V[2]: 1s
V[3]: 0.00s
V[4]: 0.00s
[Protection Para
/<n>
/V-Prot
/V[1]]
Vstart<
If the voltage falls below
this Voltage, the Time
Depending Voltage
Protection will be started.
Only available if: Device
planning: V.Mode =
Vstart< Only available if:
Device planning: V.Mode
= Vstart<
0.01 - 2.00Vn
0.90Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
V(t)<1
Pick-up value
Only available if: Device
planning: V.Mode =
V(t)<
0.01 - 2.00Vn
0.01Vn
[Protection Para
/<n>
/V-Prot
/V[1]]
t1
Tripping delay
Only available if: Device
planning: V.Mode =
V(t)<
0.00 - 10.00s
0.00s
[Protection Para
/<n>
/V-Prot
/V[1]]
Page 240
EN MRU4 10/09
Содержание HighPROTEC MRU4
Страница 1: ...MRU4 HighPROTEC Voltage Frequency Protection Device Manual DOK HB MRU4E...
Страница 3: ...Order Code EN MRU4 10 09 Page 3...
Страница 43: ...Navigation Operation Navigation Operation EN MRU4 10 09 Page 43 1 2 3 5 7 6 8 9...
Страница 307: ...Service Service General Within this menu you can initiate a reboot of the device EN MRU4 10 09 Page 307...