V 012 - Protection Module Asymmetry [47]
Parameter
Description
Setting range
Default
Menu path
V1<
Positive Phase Sequence
Undervoltage
Only available if: Device
planning: V 012.Mode =
V1<
0.01 - 2.00Vn
1.00Vn
[Protection Para
/<n>
/V-Prot
/V 012 [1]]
V2>
Negative Phase
Sequence Overvoltage
Only available if: Device
planning: V 012.Mode =
V2>
0.01 - 2.00Vn
1.00Vn
[Protection Para
/<n>
/V-Prot
/V 012 [1]]
t
Tripping delay
0.00 - 300.00s
0.00s
[Protection Para
/<n>
/V-Prot
/V 012 [1]]
VTS Blo Fc
Enabling/Disbling the
blocking by the Voltage
Transformer Supervision
module.
inactive,
active
inactive
[Protection Para
/<n>
/V-Prot
/V 012 [1]]
States of the inputs of the asymmetry module
Name
Description
Assignment via
ExBlo1-I
Module input state: External blocking1
[Protection Para
/Global Prot Para
/V-Prot
/V 012 [1]]
ExBlo2-I
Module input state: External blocking2
[Protection Para
/Global Prot Para
/V-Prot
/V 012 [1]]
ExBlo TripCmd-I
Module input state: External Blocking of the
Trip Command
[Protection Para
/Global Prot Para
/V-Prot
/V 012 [1]]
EN MRU4 10/09
Page 273
Содержание HighPROTEC MRU4
Страница 1: ...MRU4 HighPROTEC Voltage Frequency Protection Device Manual DOK HB MRU4E...
Страница 3: ...Order Code EN MRU4 10 09 Page 3...
Страница 43: ...Navigation Operation Navigation Operation EN MRU4 10 09 Page 43 1 2 3 5 7 6 8 9...
Страница 307: ...Service Service General Within this menu you can initiate a reboot of the device EN MRU4 10 09 Page 307...