Self Supervision
Error messages / -codes
After a reboot of the device the reason for rebooting will be displayed under
[Operation/Status Display/Sys/Reset].
For more information about the reboot reason please follow this chapter.
The reboot will also be logged within the event recorder. Rebooting causes an event named: Sys.reboot.
Numerical reboot codes:
Error messages / -codes
1.
Reboot after clean switching off of the device normal reboot after clean shut down of the device.
2.
Reboot by user command user-initiated reboot through panel-command.
3.
Super reset: reset to factory settings
4.
Restart by debugger;WW-SEG internally for system-analysis purpose.
5.
Restart because of configuration changes.
6.
General failure: reboot without definite reason.
7.
Reboot by SW-system abort (HOST-side); summary of several reboot reasons detected by
software, i.e. wrong pointer, corrupted files etc.
8.
Reboot by watchdog timeout (HOST-side); signaling if the protection-class-task hangs for more
than 800 ms.
9.
Reboot by system abort (DSP-side); summary of several reboot reasons detected by software,
i.e. wrong pointer, DSP-side.
10.
Reboot by watchdog timeout (DS-side);appears when DSP sequence needs longer than 3 ms for
one cycle.
11.
Loss of auxiliary voltage or low voltage reboot after loss of auxiliary voltage or voltage dropping
below reboot-level but not becoming zero.
12.
Faulty memory access: message of MMU (memory mapping unit) that prohibited memory access
has occurred.
EN MRU4 10/09
Page 309
Содержание HighPROTEC MRU4
Страница 1: ...MRU4 HighPROTEC Voltage Frequency Protection Device Manual DOK HB MRU4E...
Страница 3: ...Order Code EN MRU4 10 09 Page 3...
Страница 43: ...Navigation Operation Navigation Operation EN MRU4 10 09 Page 43 1 2 3 5 7 6 8 9...
Страница 307: ...Service Service General Within this menu you can initiate a reboot of the device EN MRU4 10 09 Page 307...