5
1.
Important Initial Information for the Technician
1.3 Boiler room/installation room
– Comply with the minimum clearances for connections, cleaning, and maintenance – see section 2.4.1 „Mini-
mum service clearances.“
– There must be sufficient ventilation into the boiler room for the safe operation of the appliance - see section
2.3 „Combustion air.“
– The boiler must only be installed in a dry, frost-free location!
– The boiler may not be installed in very dusty or humid rooms.
Permissible limit values:
Air humidity: 85 % at room temperature of 25 °C (non-condensing)
Room temperature: +2 to +40 °C
– Sufficient lighting must be provided for service and maintenance.
Attention!
The configuration of the entire system must comply with technical fire protection requirements in
accordance with the applicable regulations, standards, and guidelines.
1.4 Initial commissioning and operating instructions
Windhager Customer Service or one of our customer service partners must commission the new boiler. They will
familiarize the customer with the boiler system operation and cleaning, with reference to the operation manual.
The following preconditions must be met before ordering the boiler commissioning:
1.) Boiler installed correctly.
2.) System fully electrically wired.
3.) System rinsed, filled, and vented – heat demand must be present.
4.) Boiler connected to domestic water and filled.
5.) Sufficient quantity of fuel available (pellets, split logs, oil, or gas).
6.) The customer must be present during commissioning.
The commissioning cannot be carried out if any of these items are incomplete or neglected. The customer will
be charged for any unnecessary costs arising as a result.
Commissioning and maintenance by Windhager Customer Service or a customer service partner are part of the
guarantee requirements of the enclosed “guarantee limitations.”
Note!
Wood gasification boiler: When the boiler is heated up for the first time, unpleasant smells may
occur from gas emissions due insulation or paint residue being burnt off. Therefore, ensure that the
boiler room/installation room is well vented. Condensation may also form near the coasting sur-
faces, and the combustion chamber temperature may only increase after a delay.
Note!
Pellet boiler: During the first few weeks after start-up, condensation can occur in the combustion
chamber, ash chamber, and on the heating surfaces. This has no effect on the boiler‘s function and
service life.