8. Setting of parameters
Page 92
105204
– WTS-300-E - V4.1 - 20.01.2022
8.5
Level “Extended cleaning parameters 1” (r parameters)
Adjustment to safety elements
Def.
r10 Safety switch butterfly valve
(F40) see section 9.2
0
Parameter is hidden, if parameter [A40] = 2 or 3
0: no safety switch
1: prevents the start of cooling / cleaning, when switch is
not in proper position
2: as 1 + abort of cleaning when switch in the wrong position
r11 Cleaning pump monitoring via pressure switch
(Fault F41)
For dry running protection of cleaning pump (open in case of fault)
0: deactivated
1 .. 20: Stop cleaning after x seconds without pressure
0
r12 Cleaning pump fault thermo contact switch
(Fault F42)
To protect the cleaning pump (open in case of fault)
0: no thermo contact switch
1: thermo contact switch active
0
r18 Active cooling in after-rinsing
0
If this function is activated, the compressor is switched on in the circulation
step n84, provided that the tank temperature is between 4 ° and 40 °.
0: deactivated
1: activated with compressor lock
- see [P70]
2: activated without compressor lock
- see [P70
Detergent options
Range
Def.
r20 Dosing position
0: dosing in feed container (displacement cleaning)
1: position D1 in cleaning diagram
2: position D2 in cleaning diagram
0..2
2
r21 Detergent sequence in case of 3-cycles
see section 6.3.4
(if second main cleaning stage is deactivated)
0: only alkaline
1..10: x times alkaline, before one time acid
0..10
3
r22 Premature switching off of the rinsing pump when
adding detergent via beaker
in dosing step D1/D2 (see section 11.1)
0..120 sec.
0
Switch to level
“Extended cleaning parameters”
See section 8.1
r parameters
Code: C567
Working level
for normal daily operation
General cooling parameters
code: C212
Extended cooling parameters
code: D345
General cleaning parameters
code: B454
Extended cleaning parameters 1
code: C567
Extended cleaning parameters 2
code: D432
Service parameters
code: EA03
General tank monitor parameters
code: 4711
Extended tank monitor parameters
code: F94A
Alarm configuration
code: FFFF
Configuration
code: A384
I/O test parameters
code: 10E5