8. Setting of parameters
Page 76
105204
– WTS-300-E - V4.1 - 20.01.2022
8.2
Level “General cooling parameters” (c parameters)
Temperature settings
Range
Default
c1
c2
Target temperature for T1
Target temperature for T2
The target temperature is the temperature to
which the milk is to be cooled down. When the
target temperature is reached the compressor
switches off. See diagram.
Setting range
defined in
parameters
[P10..P13]
4,0
4,0
c10
c11
Hysteresis for target temperature 1
Hysteresis for target temperature 2
The hysteresis determines the amount by which
the milk temperature is allowed to differ from tar-
get temperature T1 or T2 before the cooling
compressor is switched on again. See diagram.
Setting range
defined in
parameters
[P15..P18]
0,7
0,7
Agitator running time settings
Range
Default
c20 Duration of after-stirring
Period in seconds for which the agitator contin-
ues to operate after compressor is switched off.
0 .. 999 sec.
120
c21 Pause duration
Period in minutes between agitator switching off
and switching on again (for the duration of the
after-stirring period selected).
0 .. 999 min.
20
c23 Duration of 'intermediate stirring SHORT'
Period in minutes during which the agitator
operates if the UP arrow button is pressed for
approx. 1 second during a cooling pause.
0 .. 999 min.
2
c24 Duration of 'intermediate stirring LONG'
Period in minutes during which the agitator
operates if the UP arrow button is pressed for
approx. 3 seconds during a cooling pause.
0 .. 999 min.
10
c25 Maximum continuous stirring period
in mode ‚continuous stirring‘
Setting of maximum continuous stirring period.
0: indefinite stirring
(to end, the OFF button must be pressed)
1..999: max. stirring period in minutes
0 .. 999 min.
30
Switch to level
“General cooling parameters”
see section 8.1
Working level
for normal daily operation
General cooling parameters
code: C212
Extended cooling parameters
code: D345
General cleaning parameters
code: B454
Extended cleaning parameters 1
code: C567
Extended cleaning parameters 2
code: D432
Service parameters
code: EA03
General tank monitor parameters
code: 4711
Extended tank monitor parameters
code: F94A
Alarm configuration
code: FFFF
Configuration
code: A384
I/O test parameters
code: 10E5
C parameters
Code: C212
Target-
temperature
Hysteresis
for T1
Hysteresis
for T2
Target-