7. Tank monitor and general fault handling
105204
– WTS-300-E - V4.1 - 20.01.2022
Page 73
7.5.5 System alarms - external sensors
F60 Error agitator monitoring
- no communication with the agitator monitoring module
See also section 9.8
F61 Error ESGSM modem / ESIPM modem
- no communication with the ESGSM or ESIPM modem
F62 Error I/O expansion module
- no communication with the I/O extension module
7.5.6 System alarms in general
F80 Low pressure error
Error is displayed if a low pressure malfunction is detected at the low
pressure input (optionally programmed)..
F81 High pressure error
Error is displayed if a high pressure malfunction is detected at the high
pressure input (optionally programmed).
F82 Fault "external fault”
Fault is displayed if a corresponding signal is present at the digital input
[A21..A33] defined as a fault indicator. Thus, external system components
can be monitored.
F83 Malfunction 4-20 mA
Error is displayed if an input current < 4 or > 20 mA is detected at the acti-
vated current input 4-20 mA.
An activated antifreeze function [A54 = 2] is temporarily deactivated in the
event of an error.
F85 Phase error
Error is displayed when the power module ESVAW-003 (if available) de-
tects a phase error.
Depending on the parameterization of the parameter [A85], the cleaning is
aborted in the event of a phase error.
7.5.7 Test alarm
F99 Test alarm
(see section 9.5)