6. Cleaning
105204
– WTS-300-E - V4.1 - 20.01.2022
Page 53
Section 6.4: Parameterization of the cleaning stages
Main circulation time: The water circulates for the pre-set time [n74]. During the
main circulating time, a post-heating temperature [n111] can be defined.
An additional time can be defined in parameter [n75], in which the drain valve
opens (agitator and cleaning pump continue to run)
Agitator and pump switch off.
Drain valve opens for the pre-set time [n76]. See also [n75].