Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
9 Troubleshooting
83054802 1/2018-07 La
214-228
Fault
codes
Diagnostic
code
Cause
Rectification
AB
01 … 3F
O
2
module has signalled a fault
01 … 0A
Internal O
2
module fault
Internal fault
(1
10
Nernst voltage of O
2
sensor outside of per-
missible range
Check electrical connection [ch. 3.3.25].
12
Voltage thermocouple of O
2
sensor outside of
permissible range
13
Voltage temperature compensation of O
2
sensor outside of permissible range
15
Temperature combustion air sensor outside
of permissible range (-20 … +800°C)
Check electrical connection and sensor
[ch. 6.10.9].
Check temperature.
16
Temperature flue gas temperature sensor
outside of permissible range
(-20 … +800°C)
17 … 1F
Internal fault O
2
module in test phase
Internal fault
(1
20
Sensor temperature of O
2
sensor too low
Check voltage supply and unit fusing of in-
ternal O
2
module.
Check voltage supply sensor heating (Q4/
Q5) [ch. 3.3.25].
21
Sensor temperature of O
2
sensor too high
Check sensor temperature [ch. 6.10.20].
22
Errors during calculation test
Internal fault
(1
23
Internal resistance of O
2
sensor less than 5 Ω
or greater than 150 Ω
Check electrical connection [ch. 3.3.25].
Replace O
2
24
Reaction time of O
2
sensor greater than
5 seconds
Check installation position of O
2
[ch. 4.1].
Clean O
2
sensor.
Replace O
2
sensor (sensor ageing).
If necessary increase O
2
control limit.
25
Error during sensor test [ch. 6.10.22]. O
2
value fluctuates, flow too low.
30
CAN-Bus connection error
Check CAN Bus and Bus connection
[ch. 5.1].
Internal fault
(1
31
CRC error of parameter page
Reset W-FM, see [ch. 9.1].
If the error occurred during a parameter
change:
Check parameter that was last changed for
plausibility.
If the reset does not achieve a fault free con-
dition:
Load data from the ABE [ch. 6.16.1].
If none of the actions listed leads to a fault
free condition:
Replace W-FM.
32
Page was open too long
33
Page has been corrupted
34
Invalid access to parameters
38
Error when copying a parameter page
3E
Invalid external default
3F
Internal plausibility fault
Internal fault
(1
B0
01, 02
Fault during output test
Internal fault
(1
B1
01
Error in short circuit testing of inputs to out-
puts
Internal fault
(1
(1
If occurring sporadically: Optimise EMC measures. If occurring continuously replace defective component.