Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
84-228
6.9 Electronic compound
6.9.1 Actuator ramps
Param & Display
RatioControl
Times
OperatRampMod
OperatRampStage
Ramp
The ramps determine the speed of the actuators for a distance of 90°. The ramp
times must not fall below the time of the slowest actuator, see actuator name plate.
Parameters
Function
OperatRampMod
Ramp time for modulating operation for phases 60 and
62. In operating position, all actuators operate at this
speed.
OperatRampStage
Ramp time for multi-stage operation for phases 60 and
62. In operating position, all actuators operate at this
speed.
Ramp
Ramp time outside the operating position for modulating
and multi-stage operation. All actuators operate at this
speed in pre-purge, ignition, post-purge and standby po-
sition.
Only in conjunction with frequency converter
The ramp time of the frequency converter must be less than the ramp time set in
the W-FM (recommendation: 30 %).
6.9.2 Shutdown behaviour
Param & Display
RatioControl
ShutdownBehav
Parameter
ShutdownBehav
determines the behaviour during lockout.
Setting
Function
Unchanged
The actuators remain in the position they were in at the
time of the lockout.
PostpurgeP
If lockout occurs, the W-FM initiates a post-purge.
HomePos
If lockout occurs, the actuators drive to standby position.