6.17 TÜV Test
6.17.1 Loss of flame
TÜV Test
LossFlameTest
Parameter
LossFlameTest
interrupts the flame signal and it is possible to
check if the W-FM initiates a lockout.
6.17.2 Safety temperature limiter
TÜV Test
SLT Test
SLT-Testload Mod
SLT-Testload Stg
These parameters can be used to check if the safety temperature limiter (STL) re-
sponds.
Parameter
SLT Test
generates a heat demand, deactivates the internal temper-
ature monitor and the burner drives to the load or stage set under
SLT-Test-
load…
.